● Adopting digital control design, and the control system is more reliable
● High power density design, capacity of single power module is 6KVA/ 10KVA/ 15KVA/ 20KVA/ 25KVA/ 30KVA/ 40KVA, the height of all these modules is 3U.The power of system ranged from 6KVA to 520KVA corresponds to the number of parallel power modules from 1 to 13
● Redundant control system, each power module is equipped independent control system, and control itself independently according to the sharing message, and the fault module separates from the system automatically
● Support parallel expansion for cabinet, and parallel expansion is up to 4 cabinets.
● Voltage of batteries can be configured flexibly, 1 input 1 output/ 3 input 1 output ±96Vdc/ ±108Vdc/ ±120Vdc(16/18/20PCS)selectable; 3 input 3 output±216Vdc/±228Vdc/±240Vdc (32/34/ 36/38/40PCS) selectable
●
MODEL | HPM1106-30KVA | HPM1110-50KVA | HPM3106-30KVA | HPM3110-50KVA | HPM3110-100KVA | HPM3320-60KVA | HPM3320-100KVA | HPM3320-200KVA | |
Capacity (VA/Watts) | UPS cabinet | 6~30k / 4.8~24k | 6~50k / 4.8~40k | 6~30k / 4.8~24k | 6~50k / 4.8~40k | 6~100k / 4.8~80k | 10~60k / 9~54k | 10~100k / 9~90k | 10~200k / 9~180k |
HPM module | 6k / 4.8k, 10k / 8k | 10k / 9k, 15k / 13.5k, 20k / 18k | |||||||
INPUT | |||||||||
Nominal voltage | 220/230Vac | 380/400Vac (3Ph+N+PE) or 220/230Vac | 380/400/415Vac, (3Ph+N+PE) | ||||||
Operating voltage range | 120~276Vac | 208~478Vac or 120~276Vac | 208~478Vac for half load; 305~478Va c for full load | ||||||
Operating frequency range | 40~70Hz | ||||||||
Power factor | ≥0.99 | ||||||||
Harmonic distortion (THDi) | 5%(100% non-linear load) | 2%(100% non-linear load) | |||||||
Bypass voltage range | 220Vac Max.voltage: +25%(optional +10%,+15%,+20% ) 230Vac Max.voltage: +20% (optional +10%,+15%) 240Vac Max.voltage: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) | 380Vac Max.voltage: +25%(optional +10%,+15%,+20% ) 400Vac Max.voltage: +20% (optional +10%,+15%) 415Vac Max.voltage: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) | |||||||
Bypass frequency range | Frequency synchronize tracing range:±10% | ||||||||
Generator access | Support | ||||||||
OUTPUT | |||||||||
Rated voltage | 220/230Vac | 380/400/415Vac(3Ph+N+PE) | |||||||
Power factor | 0.8 | 0.9/1(Customized) | |||||||
Voltage regulation | ±1% | ||||||||
Frequency | Line mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) | |||||||
Bat. mode | (50/60±0.1%)Hz | ||||||||
Crest factor | 3:1 | ||||||||
Harmonic distortion (THDv) | ≤2% with linear load ≤5% with non-linear load | ||||||||
Efficiency | 93.50% | 95.50% | |||||||
BATTERY | |||||||||
Battery voltage | ±96/±108/±120Vdc; Battery quantity(optional) | ±192/±204/±216/±228/±240Vdc; Battery quantity(optional) | |||||||
Charging current(A) | UPS cabinet | 30A (Max.) | 60A (Max.) | 30A (Max.) | 60A (Max.) | 18A (Max.) | 30A (Max.) | 60A (Max.) | |
HPM module | 6A (Max.) (Charge current can be set according to battery capacity installed) | ||||||||
Backup time | Depends on the capacity of external batteries | ||||||||
SYSTEM FEATURES | |||||||||
Transfer time | Utility to battery:0ms; Utility to bypass:0ms | ||||||||
Overload | Line mode | Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% turn to bypass mode immediately | |||||||
Bat. mode | Load≤110%: last 30S,≤125%: last 1S,≤150%: last 200ms,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 1S,≥150% shut down UPS immediately | |||||||
Bypass mode | Breaker (6kVA:40A / 10kVA:60A) | Breaker (10kVA:20A / 15kVA:32A / 20kVA:40A) | |||||||
Short circuit | Hold whole system | ||||||||
Noise suppression | Complies with EN62040-2 | ||||||||
Communication interface | UPS cabinet : RS232, RS485, Dry contact, Intelligent slot x 2(SNMP card,Relay card optional); HPM series UPS module: RS232 | ||||||||
ENVIRONMENT | |||||||||
Operating temperature | 0~40℃ | ||||||||
Storage temperature | -25~55℃ | ||||||||
Humidity range | 0~95% (Non-condensing) | ||||||||
Altitude | <1500m. When >1500m, derating power for use | ||||||||
Noise level | <55dB | <65dB | |||||||
PHYSICAL | |||||||||
Dimension D×W×H (mm) | UPS cabinet | 840×600×1400 | 840×600×2000 | 840×600×1400 | 840×600×2000 | 840×600×1400 | 1100×600×2000 | ||
HPM module | 443x580x131 (3U) | ||||||||
Net weight (kg) | UPS cabinet | 138 | 150 | 138 | 150 | 213 | 149 | 152 | 290 |
HPM module | 6kVA/23; 10kVA/25 | 10kVA/26; 15kVA/30; 20kVA/31 | |||||||
STANDARDS | |||||||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | ||||||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |