● 12 pulse rectifier technology
●3Phase In/1phase Out
●Input/output galvanic isolation
●IP31
●Input voltage window 300~500Vac and input frequency window 45~65Hz
●DC Input 220dc (-25%~+30%)
●Advance Battery auto float/boost charger, battery temperature compensation
●N+X parallel redundancy
●110%/125%/150% overload for 60min/10min/1min
●Power Walk in
●Load Bus Synchronization(LBS)
●5.7” or 7” touch-screen color monitor
●RS232, RS485(ModBus), Optional SNMP, Eight Dry contact Signals, Circuit breaker status, battery temperature sensor, etc.
●Full range from 10kVA up to 120kVA
●Perfect for oil and gas, refining, chemical, industrial power, power transmission and distribution, metallurgy, automotive, glass
● High power factor
● Wide input adaptability
● Optimized battery management
● N+X parallel redundancy
● Strong overload capability
● Power walk in
● Generator mode
● Multi-protection
● EPO function
● User-friendly network management
MODEL | EP-IND10 -ZY | EP-IND15 -ZY | EP-IND20 -ZY | EP-IND30 -ZY | EP-IND40 -ZY | EP-IND50 -ZY | EP-IND60 -ZY | EP-IND80 -ZY | EP-IND100 -ZY | EP-IND120 -ZY |
Capacity(kVA/kW) | 10/8 | 15/12 | 20/16 | 30/24 | 40/32 | 50/40 | 60/48 | 80/64 | 100/80 | 120/96 |
INPUT | ||||||||||
Nominal voltage & range(Vac) | 380/400/415 (3Ph+PE, without N)(±25%) | |||||||||
Frequency & range(Hz) | 50/60(±10%) | |||||||||
BYPASS INPUT | ||||||||||
Norminal voltage(Vac) | 220/230/240 | |||||||||
Frequency tollerance (Hz) | ±2Hz(0.5 , 1 , 2 , 3Hz settable) | |||||||||
OUTPUT | ||||||||||
Voltage (Vac) | 220/230/240±0.5% (L+N+PE) | |||||||||
Frequency | 50/60(0.5%) | |||||||||
Waveform | Pure Sinewave THDV≤1%(100% Linear load) | |||||||||
Transfer time(ms) | 0 | |||||||||
Efficiency(%) | Up to 94% | |||||||||
Overload | 110% overload for 60min;≤125% lasting 10min;≤150% lasting 1min | |||||||||
DC(BATTERY) | ||||||||||
DC voltage(Battery)(Vdc) | 220 VDC | |||||||||
ENVIRONMENTAL | ||||||||||
Operating temperature(℃) | -5~40℃ | |||||||||
Storage temperatue(℃ | ) -20~+55℃(no battery , at least keeping 4Hours to make the operation temperature up to 0℃ after -20℃ storage) | |||||||||
Humidity range | 20~95%(non condensing) | |||||||||
Altitude | ≤1500m. Refer to GB/T 7260.3 standard to execute derating when altitude is more than 1500m | |||||||||
Noise level(dB) | 58 | 60 | 62 | |||||||
OTHERS | ||||||||||
Alarm function | Output overload , utility abnormal , DC(battery)low , UPS fault alarm & history , etc | |||||||||
Protection function | Short circuit, overload , over temperatue , DC(battery)low , output low voltage , fan fault alarm | |||||||||
Communication function | RS232 , RS485(Modbus), SNMP(Optional), Dry contact car , Breaker status , Battery Temperature sensor | |||||||||
PHYSICAL | ||||||||||
Dimension(W×D×H)mm | 800×800×1800(2260 for IP31) | 1000×800×1800(2260 for IP31) | 1400×800×1800(2260 for IP31) | |||||||
Weight(kg) | 535 | 550 | 570 | 610 | 705 | 860 | 960 | 1160 | 1560 | 1650 |
STANDARDS | IEC 62040-2 CLASS C3 IEC60905-1 , IEC 6240-1-1 , UL1778 , IEC62040-3 |