● True online double conversion design
● Build-in input and output transformer with strong galvanic isolation
● Wide input range, avoid frequently transfer to battery mode, prolong the battery lifetime
● Intelligent battery management technology, fully protect battery
● Battery cold start function
● Comprehensive and reliable protection
● User-friendly network management
MODEL | UIC60L | UIC80L | UIC100L | UIC120L | UIC150L | UIC200L | UIC250L | UIC300L |
Capacity (VA/Watts) | 6k / 4.8k | 8k / 6.4k | 10k / 8k | 12k / 9.6k | 15k / 12k | 20k / 16k | 25k /20k | 30k / 24k |
INPUT | ||||||||
Nominal Voltage | 380/Vac (1±20%), (3Ph+N+PE) | |||||||
Operating Frequency Range | 50/60Hz(1±5Hz) | |||||||
Range Power Factor | >0.97(with filter) | |||||||
Max.Input Current(A) | 14 | 18 | 23 | 27 | 32 | 42 | 52 | 64 |
OUTPUT | ||||||||
Output Voltage | 220/230Vac(1±5%) | |||||||
Output Frequency | 50/60Hz(1±0.05%) | |||||||
Current crest Ratio | 3:1(Max) | |||||||
Efficiency | Online:85% | Online:85% | ||||||
Harmanic Distoriton (THDv) | <1.5% with linear load | |||||||
BATTERY | ||||||||
Battery Voltage | 192Vdc | 240Vdc | ||||||
Charging Current | 6A/12A(Optional) | |||||||
SYSTEM FEATURES | ||||||||
Transfer Time | Utility↔Battery : Oms | |||||||
Overload | >125%;last 1min;>150%;200ms tum to bypass mode | |||||||
Communication Interface | RS232,sSNMP(Optional),Dry contact(Optional) | |||||||
PHYSICAL | ||||||||
Dimension,W * D * H(mm) | 305*585*864 | 409*798**1044 | 555*741*1200 | |||||
Net Weight(48V/192V)(kg) | 100 | 108 | 110 | 118 | 178 | 200 | 300 | 310 |
ENVIRONMENT | ||||||||
Operating Temperature | 0~40°C | |||||||
Storage Temperature | ||||||||
Humidity Range | 0~95% (Non-condensing) | |||||||
Altitude | <1500m | |||||||
Noise level | <55dB | |||||||
STANDARDS | ||||||||
Safety | IEC/EN62040-1 ;IEC/EN60950-1 | |||||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |