1 phase rackmount ups 6-10kva

1 phase rackmount ups 6-10kva

  • Cname:online ups
  • Views:
  • Date:2020-04-28 11:01:30
  • Summary
  • Characteristic
  • Parameter
General Features

● True double-conversion

● Rack-mounted and floor-standing tower can be convertible

● Patented Minic LCD of which content can be rotated according to the type of deployment

● DSP technology guarantees high reliability

● N+X parallel redundancy

● Selectable quantity of battery for each group:16/18/20 pieces

● Adjustable charging current via LCD

● 3-stage charging design optimizes battery performance

● ECO mode operation for energy saving

● Self-diagnosis at startup

● Emergency power off function(EPO)

● Maintenance bypass is convenient for maintenance

● Generator compatible

● PDU is convenient for connecting load

● Communications:RS-232,USB,SNMP card(Optional), Relay card (Optional)

● Cold start

Technical Specification
MODELUBR60LUBR100L
Capacity (VA/Watts)6K / 5.4K10K / 9K
INPUT 
Nominal Voltage220/230/240Vac(L+N+PE)
Operating Voltage 
Range
120Vac-276Vac
Operating Frequency 
Range
50Hz:45~55Hz,60Hz:54~66Hz
Power Factor≥0.99
Bypass Voltage RangeMax.voltage:  220V:+25%(Optional +10%,+15%,+20% )
          230V:+20%(Optional +10%,+15%)
240V:+15%(Optional +10% )
                                   Min. voltage: -45% (Optional -20%,-30%)
ECO RangeSame as bypass
Harmonic Distortion
 (THDi)
≤5%(100% non-linear load) 
OUTPUT  
Output Voltage220/230/240Vac
Power Factor0.9
Voltage Regulation±1%
FrequencyLine Mode±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional)
Bat. Mode(50/60±0.1)Hz
Crest Factor3:1
Harmonic Distortion
 (THDv)
≤2% with linear load
≤5% with non-linear load 
Waveform Pure Sinewave
Transfer TimeUtility to Battery : 0ms; Utility to Bypass: 0ms
EFFICIENCY
EfficiencyUp to 94%
BATTERY
Battery VoltageOptional Voltage: ±96/108/120Vdc
Typical Recharge Time6-8 hours (To 90% capacity)
Charging Current Maximum current 10A; 
PROTECTION
OverloadLine ModeLoad≤125%: last 5min;≤150%: last 1min;>150% 200ms turn to bypass mode
Bypass Mode40A(Input breaker)60A(Input breaker)
Short CircuitHold Whole System
OverheatLine Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Battery Low Alarm and Switch off
INDICATORS
Audible & Visual 
alarms
Line Failure, Battery Low, Overload, System Fault
Status LED & LCD 
Display
Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Reading On The LCD 
Display
Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner 
Temperature & Remaining Battery  Backup Time
MANAGEMENT
Communication
 Interface
RS232,USB, Parallel Port, SNMPcard(Optional), Relay card (Optional)
ENVIRONMENT
Operating
 Temperature
0℃~40℃
Storage Temperature-25℃~55℃
Humidity Range0~95% (Non-condensing)
Altitude< 1500m
Noise Level<55dB
PHYSICAL
Dimension
 W×D×H (mm)
443×580×131 (3U)
Net Weight (kg)1920
STANDARDS
Noise SuppressionComplies with EN62040-2
Safety IEC/EN62040-1,IEC/EN60950-1
EMCIEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
BATTERY PACK
ModelEXBR±120V
Battery type&
 Max.quantity
7Ah×20/9Ah×20
Dimensions 
W×D×H (mm)
443×720×131 (3U)
Net Weight (kg)65/75


Label