● True double-conversion
● Rack-mounted and floor-standing tower can be convertible
● Patented Minic LCD of which content can be rotated according to the type of deployment
● DSP technology guarantees high reliability
● N+X parallel redundancy
● Selectable quantity of battery for each group:16/18/20 pieces
● Adjustable charging current via LCD
● 3-stage charging design optimizes battery performance
● ECO mode operation for energy saving
● Self-diagnosis at startup
● Emergency power off function(EPO)
● Maintenance bypass is convenient for maintenance
● Generator compatible
● PDU is convenient for connecting load
● Communications:RS-232,USB,SNMP card(Optional), Relay card (Optional)
● Cold start
MODEL | UBR60L | UBR100L | ||
Capacity (VA/Watts) | 6K / 5.4K | 10K / 9K | ||
INPUT | ||||
Nominal Voltage | 220/230/240Vac(L+N+PE) | |||
Operating Voltage Range | 120Vac-276Vac | |||
Operating Frequency Range | 50Hz:45~55Hz,60Hz:54~66Hz | |||
Power Factor | ≥0.99 | |||
Bypass Voltage Range | Max.voltage: 220V:+25%(Optional +10%,+15%,+20% ) | |||
230V:+20%(Optional +10%,+15%) | ||||
240V:+15%(Optional +10% ) | ||||
Min. voltage: -45% (Optional -20%,-30%) | ||||
ECO Range | Same as bypass | |||
Harmonic Distortion (THDi) | ≤5%(100% non-linear load) | |||
OUTPUT | ||||
Output Voltage | 220/230/240Vac | |||
Power Factor | 0.9 | |||
Voltage Regulation | ±1% | |||
Frequency | Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional) | ||
Bat. Mode | (50/60±0.1)Hz | |||
Crest Factor | 3:1 | |||
Harmonic Distortion (THDv) | ≤2% with linear load | |||
≤5% with non-linear load | ||||
Waveform | Pure Sinewave | |||
Transfer Time | Utility to Battery : 0ms; Utility to Bypass: 0ms | |||
EFFICIENCY | ||||
Efficiency | Up to 94% | |||
BATTERY | ||||
Battery Voltage | Optional Voltage: ±96/108/120Vdc | |||
Typical Recharge Time | 6-8 hours (To 90% capacity) | |||
Charging Current | Maximum current 10A; | |||
PROTECTION | ||||
Overload | Line Mode | Load≤125%: last 5min;≤150%: last 1min;>150% 200ms turn to bypass mode | ||
Bypass Mode | 40A(Input breaker) | 60A(Input breaker) | ||
Short Circuit | Hold Whole System | |||
Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | |||
Battery Low | Alarm and Switch off | |||
INDICATORS | ||||
Audible & Visual alarms | Line Failure, Battery Low, Overload, System Fault | |||
Status LED & LCD Display | Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault | |||
Reading On The LCD Display | Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner Temperature & Remaining Battery Backup Time | |||
MANAGEMENT | ||||
Communication Interface | RS232,USB, Parallel Port, SNMPcard(Optional), Relay card (Optional) | |||
ENVIRONMENT | ||||
Operating Temperature | 0℃~40℃ | |||
Storage Temperature | -25℃~55℃ | |||
Humidity Range | 0~95% (Non-condensing) | |||
Altitude | < 1500m | |||
Noise Level | <55dB | |||
PHYSICAL | ||||
Dimension W×D×H (mm) | 443×580×131 (3U) | |||
Net Weight (kg) | 19 | 20 | ||
STANDARDS | ||||
Noise Suppression | Complies with EN62040-2 | |||
Safety | IEC/EN62040-1,IEC/EN60950-1 | |||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, | |||
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | ||||
BATTERY PACK | ||||
Model | EXBR±120V | |||
Battery type& Max.quantity | 7Ah×20/9Ah×20 | |||
Dimensions W×D×H (mm) | 443×720×131 (3U) | |||
Net Weight (kg) | 65/75 |