产品banner
Kstar online ups

Kstar online ups

  • Cname:online ups
  • Views:
  • Date:2020-04-28 10:58:46
  • Summary
  • Characteristic
  • Parameter
General Features

● True double-conversion

● Digital control guarantees high reliability

● ECO mode operation for energy saving

● Output receptacle control for non-critical load shedding capability

● Emergency power off function(EPO)

● Generator compatible

● Communications:RS-232,USB,SNMP card(Optional), Relay card (Optional)

● Bypass can be used when UPS is off(Setted in LCD)

● Cold start

Technical Specification
MODELUB
10-24
UB
10
UB
10L
UB
15
UB
15L
UB
20-48
UB
20
UB
20-96
UB
20L
UB
20L-96
UB
30
UB
30-96
UB
30L
UB
30L-96
Capacity
(VA/Watts)
1000VA/900W1500VA/1350W2000VA/1800W3000VA/2700W
INPUT 
Nominal
Voltage
 208/ 220/230/240Vac(L+N+PE)
Operating
 Voltage
Range
110~300Vac @(0~60%) Load;120~300Vac @(60~70%)Load,140~300Vac @(70~80%)Load;
160~300Vac @(80~100%)Load
Operating
 Frequency
Range
50Hz:45~55Hz,60Hz: 55-65Hz  Auto Sensing
Power Factor > 0.85@25%Load;>0.95 @50%Load;>0.97@75%Load;>0.99 @ Nominal voltage& 100%Load
OUTPUT  
Output Voltage208/220/230/240Vac:230Vac(Default)
Power Factor0.9
Voltage
 Regulation
±1%
FrequencySynchronized
 Range
45-55Hz ±0.02Hz@ 50Hz, 55-65Hz ±0.02Hz@60Hz
Battery Mode
&None  
Synchronized Range 
(50/60±0.02)Hz
Crest Factor3:1
Harmonic
Distortion
(THDv)
≤3% with linear load
≤5% with non-linear load 
Waveform Pure Sinewave
Transfer TimeUtility to Battery : 0ms; Utility to Bypass: 4ms(Typical)
EFFICIENCY
AC Mode88%88%89%90%
Battery Mode84%85%85%85%86%87%
ECO Mode>93%>94%
BATTERY
Battery Type12V/9AH12V12V/9AH12V12V/9AH12V/7AH12V12V/9AH12V/7AH12V
Numbers233*N33*N4686*N8*N686*N8*N
Maximum
 Charging
 Current (A)
1.06.0/12.01.06.0/12.01.06.0/12.01.06.0/12.0
Charging
 Voltage(Vdc)
27.4V±1%41.1V±1%41.1V
±1%
54.8±1%82.2V±1%109.6V±1%82.2V±1%109.6V±1%82.2V±1%109.6V±1%82.2V±1%109.6V±1%
ProtectOver-voltage(14.7v) /Low-voltage(10v)
PROTECTION
Overlo ad 
Capacity
Line Mode105%-150%, 30s turn to bypass mode ; >150% 300ms turn to bypass mode
Battery Mode105%-150%, exceed 30s shutdown ;  >150% exceed 300ms shutdown
INDICATORS
LED & LCD DisplayLoad/Battery/Input/Output/Operating Mode Information
ALARM
Battery ModeSounding every 4 seconds 
Battery LowSounding every second
OverloadSounding every 0.5 second
FaultContinuously Sounding
MANAGEMENT
Smart RS-232/USB
(Preferential)
External Modbus card supported by RS232,Software supports Windows Family,Linus,FreeBSD
Intelligent SlotSNMP (Standard or mini) independent to RS-232(Optional)
ENVIRONMENT
Operating
Temperature
0℃~40℃
Humidity Range0~95% (Non-condensing)
Altitude< 1500m
Noise Level<50dB@ 1Meter
PHYSICAL
Dimension
 W×D×H (mm)
144×400×215191×468×337
Net Weight (kg)11.313.75.913.96.221.926.929.610.610.827.430.111.111.3
STANDARDS
Safety IEC/EN62040-1
EMCIEC/EN62040-2


Label

Prev:online ups 6-10kva2020-04-28
Next:None

Recently Viewed: